Statutory Instrument No 666 of 2006 – European Communities (Energy Performance of Buildings) Regulations 2006

BER Certificates & Poor Indoor Air Quality (III)

2009-02-27:  Energy Labelling of Industrial Products is an essential means of raising consumer awareness about energy efficiency and conservation.  I like being able to wander into an electrical shop anywhere in Ireland, Italy or Turkey, for example … and to compare the energy performance of different makes of washing machines, dishwashers or fridges … and even of apparently similar products in the different countries.

 

I can easily visualize these small industrial products being brought into a test laboratory, and then being put through their paces.  It is a credible system.

 

This is NOT possible, however, with a building.

 

 

EU Directive 2002/91/EC of the European Parliament and of the Council, of 16 December 2002, on the Energy Performance of Buildings … is a short document of 7 Pages.  Its Preamble takes up slightly more than the first 2 Pages, and there is a 1 Page Annex at the rear.  Its language is clear and straightforward (see the example of Article 4 below).

 

[What I fail to understand is how and why the Irish National Legislation which implements the Directive … Statutory Instrument No. 666 of 2006: European Communities (Energy Performance of Buildings) Regulations 2006 … is so clumsy, awkward and full of flaws … offering us yet another example of failed ‘light-touch regulation’.  It may also be unconstitutional.]

 

 

 

The EU Directive has something important to say about Indoor Air Quality

 

Article 4 – Setting of Energy Performance Requirements

 

1. Member States shall take the necessary measures to ensure that minimum energy performance requirements for buildings are set, based on the methodology referred to in Article 3.  When setting requirements, Member States may differentiate between new and existing buildings and different categories of buildings.  These requirements shall take account of general indoor climate conditions, in order to avoid possible negative effects such as inadequate ventilation, as well as local conditions and the designated function and the age of the building.

 

[Quick flashback to a generation ago … the panic, throughout Europe, to conserve energy in the late 1970’s and early 1980’s led to a dramatic reduction in rates and quantities of direct, natural ventilation to the habitable spaces of buildings.  This, in turn, had an adverse impact on Indoor Air Quality, and led to a sharp rise in Asthma among building occupants.]

 

 

 

In Ireland, today, problems concerning Poor Indoor Air Quality continue to occur … typically during the Winter Heating Season.  There is a natural tendency to keep windows closed and to seal permanent ventilation openings.  Accidental indoor air seepage to the exterior is also being reduced in our newer building stock.

 

Poor Indoor Air Quality, an important factor in relation to building related ill-health (also known as ‘sick building syndrome’), can cause serious health impairments and severely restrict a person’s participation in everyday activities, e.g. work.

 

Symptoms and Signs may include:

         irritation of eyes, nose and throat ;

         respiratory infections and cough ;

         voice hoarseness and wheezing ;

         asthma ;

         dry mucous membrane and skin ;

         erythema (reddening or inflammation of the skin) ;

         lethargy ;

         mental fatigue and poor concentration ;

         headache ;

         stress ;

         hypersensitivity reactions, i.e. allergies ;

         nausea and dizziness ;

         cancers.

 

 

 

The following 2 Performance Indicators of Good Indoor Air Quality, developed with the aim of protecting human health, are recommended:

 

         Carbon Dioxide (CO2) concentrations in a building should not significantly exceed average external levels – typically within the range of 300 to 500 parts per million – but should at no time exceed 800 parts per million ;

 

         Radon Activity (including Rn-222, Rn-220, RnD) in a building should, on average, fall within the range of 10 to 40 Bq/m3 … but should at no time exceed 60 Bq/m3.

 

 

NOTES:

 

The concept of Protecting Human Health is altogether different from the concept of Assessing Risk to Safety.

 

In Ireland, testing for Radon Activity in buildings must take place during the Heating Season, i.e. the months of November through to March.  What is the use of testing during July, for example, when windows will be wide open ?   Who would even think of doing that ?   I wonder.

 

Measurement Uncertainty of the standard Alpha Particle Etched-Track Detector distributed by the Radiological Protection Institute of Ireland (RPII) is as follows:

         under laboratory conditions: …………………… in the order of …… +/- 10%

         under tightly controlled site conditions: …. in the order of …… +/- 20%

         under typical conditions of use: …………….. well in excess of … +/- 30%

 

Unfortunately, until the RPII includes proper statements of Measurement Uncertainty in its Test Reports … our Organization cannot recommend RPII Radon Testing Services, and we will not accept RPII Test Reports as proper evidence of Radon Test Results.

 

.

 

.

 

END

Enhanced by Zemanta

BER Certificates, Legislation & Thermal Comfort (I)

2009-02-20:  The recent comment submitted by Mr. Robin Evans regarding the use of Infra-Red Thermography as an aid to BER Assessment … and the high level of confusion and misinformation in the marketplace, which I have now had an opportunity to examine more closely … have forced me to conclude that a series of posts on BER Certificates would be good for the system – ‘my’ system !

 

There are many pieces in this jig-saw puzzle, but the final picture is wonderful … please believe me.

 

 

Before I start to assemble anything, however, a few small details …

 

         Infra-Red Thermography.  This is a valuable technical aid during any Energy Survey of any Building.  It is remarkable how much information can be gathered by a good, high-resolution Infra-Red Camera.  But, it must be used competently …  Because we are working in ambient temperature conditions, i.e. between -10OC and +30 OC, it should be a Long Wave Infra-Red Camera (≈ 8-12 microns).  The temperature difference between the inside of the building and the exterior should be at least 10 degrees C … it would be better with 15 degrees C.  The Camera Operator should be fully familiar with the operation of the Camera and its associated computer software, etc … and he/she should know what they are looking at.  In other words, some sort of architectural background is essential … not only are images taken outside the building, but they are also taken inside the building !   Any Camera Work should be done after dark.  It is not necessary to do a midnight to 4 o’clock in the morning shift … 8 o’clock in the evening until midnight is perfectly fine.  By the way, none of this work can be done in just 30 minutes.  Finally, Infra-Red Work is best carried out, in Ireland, during the Heating Season, i.e. the months of November through to March.  Depending on the year, it may be possible to squeeze in the end of October and the beginning of April.

 

In the old days, I used to work as part of a Multi-Disciplinary Team of 4 People (not all males !), comprising a Civil Engineer, a Physicist/Expert in Measurement, an Engineering Technician with a background in Social Science, and myself as Architect/Fire Engineer/Technical Controller.  They were great days !

 

 

Robin … in order to provide this service for the owner of a typical suburban, semi-detached house … €100 (Euros) is a little on the low side, even as a ‘lost leader’.

 

And … the Irish Public are indeed blissfully unaware of the efficacy of Infra-Red Thermography.  The ‘powers that be’ in Ireland, i.e. the Department of the Environment, Heritage & Local Government (DEHLG), Energy Ireland (SEI) and the Construction Industry Federation (CIF), are not at all interested in the ‘real’ energy performance of buildings.  They have a vested interest in not being interested.  Suddenly … the image of an ostrich, with head deeply embedded in sand, floods my mind …

 
Colour Clip Art Image of an Ostrich, with head deeply embedded in sand. Meanwhile, in the background, an hourglass signals that time is running out !
Colour Clip Art Image of an Ostrich, with head deeply embedded in sand. Meanwhile, in the background, an hourglass signals that time is running out !

  

         BER Certificates & EU/National Legislation.  Mr. Charlie McCreevy, Ireland’s EU Commissioner, during one of his many ‘direct, pragmatic and neo-liberal’ talks in Dublin, used the following magnificent phrase in relation to the national implementation of European Union Legislation in the different EU Member States … ‘National Gold Plating and Divergent Implementation’ … some important words to remember !   However, I learned this valuable lesson myself a long, long time ago.

 

Irish National Legislation:  Statutory Instrument No. 666 of 2006: European Communities (Energy Performance of Buildings) Regulations 2006.

 

These Regulations may be unconstitutional.  A prime example … Section 23 (1) states that a person authorised by Energy Ireland (SEI) under the Regulations … ‘may enter, inspect and examine a building or any part of a building for the purpose of forming an opinion as to whether or not a BER Data File or BER Certificate issued for the building, or part of the building, is warranted’.  In relation to a private, single-occupation dwelling house … this provision is entirely unacceptable !

 

The Register of BER Assessors on the SEI WebSite is not reliable.

 

Because of ‘national gold plating and divergent implementation’ in Ireland, it is necessary to be familiar, also, with the originating EU Secondary Legislation.

 

European Union Legislation:  EU Directive 2002/91/EC of the European Parliament and of the Council, of 16 December 2002, on the Energy Performance of Buildings.

 

Both pieces of legislation can be downloaded from the SDI WebSite … here.

 

 

         Thermal Comfort in Buildings.  The starting point for any discussion about this subject should be an International Standard, which is also the European Standard and the Irish National Standard … ISO 7730  Moderate Thermal Environments – Determination of the PMV and PPD Indices and Specification of the Conditions for Thermal Comfort.

 

This Standard establishes the following important general principle … and is also critical in relation to people with activity limitations who use/occupy/visit buildings: Man’s/Woman’s Thermal Sensation is mainly related to the thermal balance of his/her body as a whole.  This balance is influenced by his/her physical activity and clothing, as well as the environmental parameters: air temperature, mean radiant temperature, air velocity (i.e. draughts) and air humidity.

 

Air Temperature, alone, is definitely not an Indicator of Thermal Comfort in a building.

 

 

         Technical Control of Construction.  The 2005 & 2008 NIST Reports on the 9-11 WTC Incident have presented us with some stark language … ‘NIST urges state and local agencies to rigorously enforce building codes and standards since such enforcement is critical to ensure the expected level of safety … unless they are complied with, the best codes and standards cannot protect occupants, emergency responders, or buildings.’

 

With regard to Private Construction in Ireland … Building Control Authorities in Ireland are, purposefully, not sufficiently resourced to be ‘effective’.  See my earlier Post, dated 2009-02-12.

 

With regard to Public Construction in Ireland … self-regulation is no regulation !  Government Departments, the Office of Public Works and Local Authorities can, far too often, be complacent, careless and/or stubborn concerning compliance with even the minimal performance levels specified in building regulations, codes and standards.

 

.

 

.

 

END

Enhanced by Zemanta

Building Energy Rating (BER) Certificates – Worried ?

2008-12-12:  Thursday, 1 January 2009, is fast approaching, and any person offering an existing house for sale or rent around this time is being bombarded by all sorts of ‘marketing blurbs’ in the different media about having to produce a BER Certificate.

 

Don’t be worried.

 

When in doubt, go directly to the actual legislation … and in this case, it is Statutory Instrument No.666 of 2006: European Communities (Energy Performance of Buildings) Regulations 2006.

 

Legislation cannot be retrospective … so, if a house has already been offered for sale or rent before 1 January 2009, no BER Certificate is required.

 

 

BER Certificate Ireland
Colour image of an Irish BER Certificate. See S.I. No.666 of 2006: European Communities (Energy Performance of Buildings) Regulations. Click to enlarge.

 

And … if you care to look at the text on one of these ‘certificates’ (in the top right-hand corner), you will notice the following …

 

” The Building Energy Rating (BER) is an indication of the energy performance of this dwelling.”

 

However, unless long wave infra-red thermography has been used under proper conditions, by a competent person, as part of a comprehensive energy survey of the house … and thermal images were taken … and other accurate and precise information was gathered about the actual energy performance of this specific house … the statement in the BER Certificate is misleading.

 

There is only a very tenuous relationship between a BER Certificate and the ‘real’ energy performance of a specific building.

 

What’s more …. Energy Ireland (SEI) knows full well that this is the case.

 

 

In addition, as if that were not bad enough …. Energy Ireland (SEI) have been sitting on a Report for approximately 3 years which indicates that there is a general non-compliance rate of 70% (that’s right folks !) with the minimal – some might say “abysmal” – energy performance requirements, which apply to new houses, in Part L of the Irish Building Regulations.

 

And …. because everybody can see that our national system of building/technical control in Ireland is entirely inadequate, that figure of 70% non-compliance may be an underestimate.

 

Many, many months ago, I asked for a copy of this SEI Report.

 

I am still waiting.

 

 

[2009-01-12   Who did I ask ?   Mr. Brendan Halligan, SEI Board Chairperson & Mr. Kevin O’Rourke, SEI Head of Built Environment !]

 

.

 

.

 

END